Ultra-Aire 70H Installer’s & Owner’s Manual
10.4 Compressor/Capacitor Replacement
This compressor is equipped with a two terminal external
overload and a run capacitor, but no start capacitor or relay.
CAUTION
CAUTION-ELECTRICAL SHOCK HAZARD: Electrical power
must be present to perform some tests. These tests
should be performed by a qualified service person.
10.5 Electric Ventilation Damper
The damper will open when the ventilation is called for,
allowing fresh air into the structure through the fresh air
inlet duct. The electric ventilation damper will remain closed
when the ventilation is not activated in order to prevent over-
ventilating the structure when the unit is dehumidifying or
recirculating the indoor air. The electric ventilation damper
operates on 24 Vac from the control circuit. DO NOT connect
high voltage to the damper motor or damage to the motor
will result. DO NOT force the blade of the damper by hand or
damage to the damper motor may result.
The damper opens in one direction only. The damper rotates
very slowly, allow sufcient time for the damper to cycle. The
damper will take approximately one minute to cycle from
closed to open or from open to closed.
If the electric ventilation damper fails to operate:
1. Check that the wiring is correct and that voltage is
present at the damper motor.
2. Check for any obstruction inside the damper. If the
electric ventilation damper fails to operate after
performing these checks, it must be replaced.
FOR HVAC INSTALLER ONLY